SE56

28

MENU 6 - OUTPUTS

(POS. 6.1) Function choice corresponding to on/off output 1

[Out1=XXXXXX]

Function choice corresponding to digital Output 1. The functions are listed in the table below.
(POS. 6.2) Function choice corresponding to on/off output 2

[Out2=XXXXXX]

Function choice corresponding to digital Output 2. The functions are listed in the table below.

(POS. 6.3) Current output option and range

[Out mA=X_XX XXX]

This function sets the current output N.1. This function is optional and will not appear unless the
option has been requested. There are three fields to modify for this function:
• Scale

zero:

4 or 0mA

• Full

scale:

20 or 22mA

• Field:

+ = positive, - = negative, blank = both, -0+ = central zero scale

The values corresponding to the scale points are shown in the following chart:

In hardware alarm conditions “HARDW AL.” (interrupted coils, empty pipe, measure error) the
current value is programmed by the function “mA v.fault” (pos. 4.4) and it is expressed as
percentage of a fixed current range, where: 0% = 0mA and 110% = 22mA.

CURRENT VALUES IN mA ASSOCIATE TO THE % FULL SCALE VALUE

POSSIBLE FIELD

REVERSE FLOW VALUE

ZERO

DIRECT FLOW VALUE

-110% -100% 0%

+100%

≥+110%

OutmA = 0 - 20 +

0

0

0

20

20

OutmA = 0 - 22 +

0

0

0

20

22

OutmA = 4 - 20 +

4

4

4

20

20

* OutmA = 4 - 22 +

4

4

4

20

22

OutmA = 0 - 20 -

20

20

0

0

0

OutmA = 0 - 22 -

22

20

0

0

0

OutmA = 4 - 20 -

20

20

4

4

4

OutmA = 4 - 22 -

22

20

4

4

4

OutmA = 0 - 20

20

20

0

20

20

OutmA = 0 – 22

22

20

0

20

22

OutmA = 4 - 20

20

20

4

20

20

OutmA = 4 – 22

22

20

4

20

22

OutmA = 0 - 20 –0+

0

0

10

20

20

OutmA = 0 - 22 –0+

0

1

11

21

22

** OutmA = 4 - 20 –0+

4

4

12

20

20

OutmA = 4 - 22 –0+

4

4.8

12.8

20.8

22

FUNCTIONS FOR OUTPUTS 1 AND 2

‰

OFF: DISABLED

‰

#1 IMP+: PULSE ON CHANNEL 1 FOR POSITIVE FLOW RATE

‰

#1 IMP-: PULSE ON CHANNEL 1 FOR NEGATIVE FLOW RATE

‰

#1 IMP: PULSE ON CHANNEL 1 FOR POSITIVE AND NEGATIVE FLOW RATE

‰

#2 IMP+: PULSE ON CHANNEL 2 FOR POSITIVE FLOW RATE

‰

#2 IMP-: PULSE ON CHANNEL 2 FOR NEGATIVE FLOW RATE

‰

#2 IMP: PULSE ON CHANNEL 2 FOR POSITIVE AND NEGATIVE FLOW RATE

‰

#1 FREQ+: FREQUENCY CHANNEL 1 FOR POSITIVE FLOW RATE

‰

#1 FREQ-: FREQUENCY CHANNEL 1 FOR NEGATIVE FLOW RATE

‰

#1 FREQ: FREQUENCY CHANNEL 1 FOR POSITIVE AND NEGATIVE FLOW RATE

‰

#2 FREQ+: FREQUENCY CHANNEL 2 FOR POSITIVE FLOW RATE

‰

#2 FREQ-: FREQUENCY CHANNEL 2 FOR NEGATIVE FLOW RATE

‰

#2 FREQ: FREQUENCY CHANNEL 2 FOR POSITIVE AND NEGATIVE FLOW RATE

‰

SIGN: FLOW DIRECTION OUTPUT (ENERGIZED = -)

‰

RANGE: RANGE INDICATION OUTPUT (ENERGIZED = SCALE 2)

‰

MAX AL.: MAX FLOW RATE OUTPUT(ENERGIZED = AL. OFF)

‰

MIN AL.: MIN FLOW RATE OUTPUT(ENERGIZED = AL. OFF)

‰

MAX+MIN: MAX AND MIN FLOW RATE ALARM OUTPUT (ENERGIZED = AL. OFF)

‰

P. EMPTY: EMPTY PIPE ALARM OUTPUT (ENERGIZED = FULL PIPE)

‰

OVERFLOW.: OUT OF RANGE ALARM OUTPUT (ENERGIZED = FLOW RATE OK)

‰

HARDW AL.: CUMULATIVE ALARM OUT interrupt coils, empty pipe, measure error (ENERGIZED=NO ALARM)