In this menu item, the features of the sensor such as approval, process
fitting, seal, measuring range, electronics, housing and others are
displayed.

6

.2 Adjustment menu 4 … 20 mA/HART

To damp process-dependent measured value fluctuations, you have to
set an integration time of 0 … 999 s in this menu item.

Depending on the sensor type, the factory setting is 0 s or 1 s.

In the menu item "Current output mode" you determine the output
characteristics and reaction of the current output in case of failure.

The default setting is output characteristics 4 … 20 mA, failure mode
< 3

.6 mA.

In the menu item "Current output Min./Max.", you determine the
reaction of the current output during operation.

The default setting is min. current 3.8 mA and max. current 20.5 mA.

Instrument features

Setup/Damping

Setup/Current output
mode

Setup/Current output
Min./Max.

Indicating and adjustment module

27

6

Setup - sensors from software 4.0.0

41787

-

EN

-