Burkert Type 8186 User Manual

Page 29

Advertising
background image

2

Select the requested simulation variable with [->] and confirm with
[OK]

.

3

With [OK] you start the simulation, first of all the actual measured
value is displayed in %

4

Start the editing mode with [OK]

5

Set the requested numerical value with [+] and [->].

6

Push [OK]

Note:
During simulation, the simulated value is outputted as 4 … 20 mA
current value and digital HART signal.

How to interrupt the simulation:

à Push [ESC]

Information:
The simulation is terminated automatically 10 minutes after the last key
has been pushed.

The sensor offers the HART modes standard and Multidrop. In this
menu item you determine the HART modes and enter the address with
Multidrop.

The mode standard with the fixed address 0 means output of the
measured value as 4 … 20 mA signal.

In Multidrop mode, up to 63 sensors can be operated on one two-wire
cable. An address between 1 and 63 must be assigned to each
sensor.

8

)

The default setting is standard with address 0.

8

)

The 4 … 20 mA signal of the HART sensor is switched off. The sensor
consumes a constant current of 4 mA. The measuring signal is transmitted
exclusively as digital HART signal.

Further settings/HART
mode

Indicating and adjustment module

29

6

Setup - sensors from software 4.0.0

41787

-

EN

-

120316