Jog forward, Jog reverse – CONTREX CX-1200 User Manual

Page 19

Advertising
background image

Page 17

Run

(J6 pins 5, 3)
Digital Input 3

When the Run input (J6, pin 6) is momentarily shorted
to common, the CX-1200 enters the Run state. As a
momentary input, Run is internally latched and does
not need to be maintained closed by an operator
device.

NOTE: Close the R-Stop, H-Stop, and F-Stop inputs

prior to entering the Run state. If you are only
using one of the Stop inputs, wire short the
other Stop inputs to the common or the CX-
1200 will not enter run.

Jog Forward

(J6 pins 6, 8)
Digital Input 4

Jog Forward is a maintained input. When it is closed,
it sends a forward speed command signal to the drive
at the selected Jog Setpoint. As a maintained input,
Jog Forward is only active when the operator device is
closed.

NOTE: Close the R-Stop, H-Stop and F-Stop inputs

prior to entering the Jog state. If you are only
using one of the Stop inputs, wire short the
other Stop inputs to the common or the
CX-1200 will not enter Jog.

Jog Reverse

(J6 pins 7, 8)
Digital Input 5

Jog Reverse is a maintained input. When it is closed,
it sends a reverse speed command signal to the drive
at the selected Jog Setpoint. As a maintained input,
Jog Reverse is only active when the operator device is
closed.

NOTE: Close the R-Stop, H-Stop and F-Stop inputs

prior to entering the Jog state. If you are only
using one of the Stop inputs, wire short the
other Stop inputs to the common or the
CX-1200 will not enter Jog.

Figure 18 Run

RUN

3

5

J6

Com

DI_3

Figure 19 Jog Forward

JOG FORWARD

6

8

J6

DI_4

Com

Figure 20 Jog Reverse

JOG REVERSE

7

8

J6

DI_5

Com