CONTREX MLP-Trim User Manual

Page 58

Advertising
background image

3 - 18

Master Mode Analog Setpoint Example

The following example demonstrates Master mode scaling using analog setpoint:

A pump delivers 20.0 gallons per minute when the pump motor rotates
at 1800 RPM. The pump motor is equipped with a 60 tooth ring kit
feedback sensor. The pump will run at 20.0 gallons per minute with an
analog input of 10 volts.

Table 3-13 Master Mode Setpoint Allocation Example

CP

Parameter Name Value Remarks

CP-84

Analog Input
Allocation

CP-20

Master Engineering
Units

CP-34

Max RPM Feedback

CP-31

PPR Feedback

Allocates the analog input as
Master Setpoint 1.

This is the Engineering Unit value
that would be present if the analog
input were at 10.0 volts.

The maximum operating RPM of
the feedback shaft.

Feedback sensor resolution.

4

20.0

1800

60