Follower Mode Analog Lead Example

The following example demonstrates Follower mode scaling using analog lead:

A pump delivers 20.0 gallons per minute of ingredient A when the pump
motor rotates at 1800 RPM. A second pump delivers 40.0 gallons per
minute of ingredient B when the pump motor rotates at 1800 RPM. A
potentiometer connected to the analog input of the MLP-Trim produces
a 10.0 volt signal when the pump A (lead) motor rotates at 1800 RPM.
The following motor B has an encoder feedback of 30 PPR. The Fol-
lower setpoint is to reflect the flow ratio in gallons/minute of ingredient B
to ingredient A.

Table 3-21 Follower Mode Lead Allocation Example

CP

Parameter Name Value Remarks

CP-84

Analog Input
Allocation

CP-21

Follower
Engineering Units

CP-34

Max RPM Feedback

CP-31

PPR Feedback

Allocates The analog input as the
lead source.

This is the Engineering Unit value
that would be present if the analog
input were at 10.0 volts and the
feedback at Max RPM Feedback.

40.0 gal/min (ingredient B) = 2.000
20.0 gal/min (ingredient A)

The maximum operating RPM of
the feedback shaft.

The resolution of the feedback
sensor.

1

2.000

1800

30