3 - 32

Table 3-23 Entering Follower Scaling Analog Feedback Parameters

CP

Parameter Name

Parameter Value

CP-84

Analog Input Allocation

CP-21

Follower Engineering Units

CP-33

Max RPM Lead

CP-30

PPR Lead

Setting CP-84 to a value of "2"
allocates the analog input to be used
as the feedback signal.

Enter the Follower Engineering Unit
value for an analog feedback level of
10.0 volts and lead of Max RPM Lead
(CP-33).

Enter the maximum operating RPMs
measured at the lead sensor shaft.

Enter the resolution of the lead
sensor.

Note:

The Max RPM Feedback (CP-34) and PPR Feedback (CP-31) control param-

eters, used for scaling Follower mode with a frequency lead, are ignored when
using analog feedback scaling.