Micromod Micro-DCI: 53SL6000 Single Loop Controller User Manual

Page 17

Advertising
background image

Analog Output 1

(referenced to power common)

Number

1

Rated Signal Range

0/4 to 20 mA

Control Range

0 to 21.5 mA

No-Load Voltage

24 V

Load Range

0 to 750 ohms

Filter Time Constant

50 ms

Output Measurement
Error

≤ ±

0.02 mA

Temperature Effects

≤ ±

0.002 mA/

°

C

Discrete Outputs 1 and 2

(open drain tied to power common)

Number

2

(Contact ratings are for resistive
loads; transient suppression is re-
quired for reactive loads.)

Open (off)

1 mA leakage

Closed (on)

2.0 V dc maximum voltage drop,
50 mA maximum operating cur-
rent,
30 V dc maximum operating volt-
age, and
100 mA maximum short circuit
current

Universal Analog Input Option Module

(Isolated inputs, see Common Mode Rejection in
High/Low Level Input chart on next column)

Number

Single: 1 input module,
Dual: 2 input module

Update Rate

300 msec

General Input Types

Low Level - mV, RTDs,
thermocouples
High Level - voltage, current,
frequency, pulse

Input Ranges

1 to 5 V linear
1 to 5 V square root
0 to +5 V square root
0 to

±

80 mV

Frequency input 8 Hz - 100 kHz
Frequency input 2.5 Hz - 100 kHz
Frequency input 0.5 Hz - 30 kHz
Pulse input (incremental sum)
0-100 kHZ

Input Ranges (cont)

RTD - 3 or 4 wire connection (see
list)
Thermocouple (see list)

High/Low Level Input Specifications

Low Level Input

High Level Input

Input Connection Differential

Differential

Input Range:

±

83 mV

±

5.3 V

Input Resistance: 10 Mohm

800 Kohm

Filter - 3db Point: 4.0 Hz

no filter

Filter Response
(63%):

0.025 sec

N/A

Normal Mode
Rejection:

24 db @ 60 Hz,
22 db @ 50 Hz

N/A

Common Mode
Rejection:

160 db

160 db

Common Mode
Operating:

250 V rms

250 V rms

Normal Mode
Maximum:

250 V rms

< 25 V

Conversion Type: Volts to

frequency

Volts to
frequency

Resolution (17
bits plus sign):

2.5618 uV

0.1636 mV

Analog
Measurement
Error:

±

0.1% F.S.

±

25 ppm/°C

±

0.1% F.S.

±

25 ppm/°C

Frequency
Measurement Error

0.01%

Frequency Input

Pulse, Square Wave:

Requirement

+5 V, 5 usec-minimum
Sine, Triangular Wave:
10 V p-p

Pulse Measurement
Error

0%

Thermocouple

Internal CJC

CJC Measurement
Error

±

2

°

C

RTD List

Platinum RTDs

Platinum 100 Ohm RTD

α

= 0.003850

-200

°

to +850

°

C

(-320

°

to 1560

°

F)

Platinum 100 Ohm RTD

α

= 0.003926

-200

°

to +870

°

C

(-320

°

to 1590

°

F)

Platinum 100 Ohm RTD

α

= 0.003911

-200

°

to +850

°

C

Section 1. Introduction

53SL6000 Instruction Manual

1-5

Advertising