Micromod Micro-DCI: 53SL6000 Single Loop Controller User Manual

Page 95

Advertising
background image

8.4.4 D02 - PV1 Low Alarm Contact
Out

D02 is closed (on) when the alarmed process vari-
able value, PV1, is not within the process alarm
limit 2 (PL2) setting.

Applicable parameter that may require configura-
tion change:
Section 5.6, ProG-do-inV2.

8.4.5 DI1 Force Output Contact Input

This is a closed contact or low active signal (0-1 V
dc). When a closed contact or 0-1 V dc signal is
present on this input, the control output value is
applied to the value of Ai7 (the control scheme D
input accepts the force control value and cS.d is
defaulted to select Ai7).

Applicable parameters that may require configura-
tion changes:
To enter a Force Output value in register Ai7:
Section 5.2, ProG-Ai-Ai.7 or oPEr-Ai7.

8.4.7 A01 - PV2 Re-Transmit (Auto)

This is the selected analog 4-20 mA output signal
that is sent to the final control element.

Applicable parameters that may require configura-
tion changes:
Section 7.7, conF-cn.1-(oh, oL, hML, oSr, rSW,
rSV).
For control related prompts:
Section 7.7, conF-cn.1-(ir, iLr).

8.4.8 SchM Selection

The auto/manual selector is implemented with the
c o n tr o ll er d ef au lt se tt in gs an d i n. Ld ( in di ca-
tor/loader) selected from the SchM prompt of the
cS module.

Applicable parameter that may require configura-
tion changes:
Section 7.6, ProG-cS-SchM.

53SL6000 Instruction Manual

Section 8. Eight Control Strategies

8-8