Micromod Micro-DCI: 53SL6000 Single Loop Controller User Manual

Page 47

Advertising
background image

Table 5-3. Input Type Prompts

(conF Menu

Ai.3, Ai.4 Modules)

Prompt

Description

See

Table

dtot

Delta Pulse Totalizer (pulse input,
incremental sum) 0-100 kHz

5-7

Table 5-4. Volt/Millivolt Input Types

(conF Menu

Ai.3, Ai.4 Modules)

Prompt

Description

Dft

tYPE

Make prompt selection from Table
5-3. Applicable types are:
0-5V, 1-5V, 0-80.

1-5V

SPAn

ZEro

Engineering Span, Engineering Zero
These values set the engineering
unit representation of the input
signal over the input range.

Ai

= SPAn 

input%

100

+ ZEro

100.0

0.0

dFLt

Digital Filter
Specifies the time constant in
seconds for a first order filter
through which the input is
processed. The filter dampens the
higher frequency signal
components usually associated with
noise. Selections:

nonE

4.2

75.0

1200

0.3

9.0

150.0

2400

0.6

18.6

300.0

1.8

37.2

600

nonE

SQrt

Square Root Signal
Speciifies whether the analog input
signal requires square root
characterization (as would be the
case for a differential pressure
transducer across an orifice plate),
or linear interpretation. Selections:
Lin: Linear interpretation.
SQrt: Square root characterization.
(For SQrt selection, the value
of Ai is forced to 0.0 at low
input signal levels [<6.25%] to
prevent large signal
oscillations.)

Lin

Table 5-5. Thermocouple Types

(conF Menu

Ai.3, Ai.4 Modules)

Prompt

Description

Dft

tYPE

Make prompt selection from Table
5-3. Applicable types are:
J.tc

S.tc

V.tc

\S.tc

K.tc

b.tc

F.tc

PL.tc

t.tc

n.tc

G.tc

E.tc

c.tc

d.tc

r.tc

L.tc

\E.tc

1-5V

dFLt

Digital Filter
Specifies the time constant in
seconds for a first order filter
through which the input is
processed. The filter dampens the
higher frequency signal
components usually associated with
noise. Selections:

nonE

4.2

75.0

1200

0.3

9.0

150.0

2400

0.6

18.6

300.0

1.8

37.2

600

nonE

dEG

Temperature Scale
Input selections are as follows:
c: Celsius scale.
F: Fahrenheit scale.

c

Table 5-6. RTD Types

(conF Menu

Ai.3, Ai.4 Modules)

Prompt

Description

Dft

tYPE

Make prompt selection from Table
5-3. Applicable types are:

Pt.85

53.c

PT.91

100.c

Pt.92

100.n

10.c

120.n

1-5V

dFLt

Digital Filter
Specifies the time constant in
seconds for a first order filter
through which the input is
processed. The filter dampens the
higher frequency signal
components usually associated with
noise. Selections:

nonE

4.2

75.0

1200

0.3

9.0

150.0

2400

0.6

18.6

300.0

1.8

37.2

600

nonE

dEG

Temperature Scale
Input selections are as follows:
c: Celsius scale.
F: Fahrenheit scale.

c

rtd

RTD Termination
Input selections are as follows:
3.trM: 3 wire.
4.trM: 4 wire.

3.trM

Section 5. Inputs/Outputs (I/O)

53SL6000 Instruction Manual

5-3

Advertising