Sense Input / Trigger Output

RS-232 / IR / A-Net Control

Symptom

Possible Cause

Solution

Conditional power
command for
monitor not
working properly

1. Conditional programming incorrect

1.

Verify/correct programming in the ATON configuration
software

2. Sensor faulty or not connected

properly

3. Incorrect Sensor being used

2.

Verify/correct Sensor operation and connection.

3.

Use correct sensor

System Trigger Out
not working
properly

1. Faulty or incorrect 3.5mm cable

being used.

2. Check for 12VDC with multi-meter

1.

Correct wiring – Use a MONO 3.5mm cable.

2.

100mA maximum current

Symptom

Possible Cause

Solution

Zone IR receive LED
does NOT flash
when a button is
pressed.

1. IR controller not programmed.

1. Program IR controller or correct programming.

2. IR signal path wiring bad.

2. Verify IR signal path wiring. Check touchpads, IR

sensors, AH66T IR Input jack, etc.

Intermittent control
from IR controller.

IR flooding.

Zone IR receive LED glowing or flickering when no
commands are being sent indicates IR flooding.
Possible sources: ambient light or plasma / LCD TV
flooding.

A-Net commands
not working

1. A-Net wiring incorrect.

1. Verify wiring.

2. Chassis unit ID set incorrectly.

2. Set chassis unit ID correctly. (See page 47)

3. Incorrect commands

3. Verify / Correct programming

3

rd

Party RS-232

commands not
working

1. No connection from RS-232

controller to the AH66t

2. Faulty connection / incorrect pin

configuration

3. AH66T RS-232 configuration not

correct for the RS-232 controller
being used

1. Connect RS-232 controller

2. Correct wiring / Verify correct DB-9 to RJ45 adapter is

being used (

DB9F-RJ45 NULL Modem)

3. Configure the correct settings using the ATON

configuration software