963 User Guide TC200635 Issue 3 25/03/2008

31

3.3 Adjust

Values

3.3.1 Adjust Knob Values

3.3.1.1 Adjust a Knob in a Trend Device

The value of knobs in Trend devices can be adjusted from a schematic page or from the Device Viewer.

To adjust a knob in a Trend device:

1. Display the page containing the knob that is to be adjusted and click the button that enables it to be

changed.

Or

View the knob that is to be adjusted in the Device Viewer, right-click the knob, and click Adjust Point.

2. At this point you may be asked if you are sure you want to make the adjustment click Yes.

A dialogue box is displayed.

3. Enter the new value by typing it in, clicking the numbers, or clicking << or >> to decrement/increment the

value.

4. Click Enter.

3.3.1.2 Adjust a Knob (Analogue Value) in a BACnet Device

Analogue values in a BACnet devices are represented in 963 as knobs, these can be adjusted from a schematic page
or from the Device Viewer.

To adjust knob (analogue value) in a BACnet device:

1. Display the page containing the knob representing the analogue value that is to be adjusted and click the

button that enables the value to be changed.

Or

View the knob representing the analogue value that is to be adjusted in the Device Viewer, right-click the
knob, and click Adjust Point.

2. At this point you may be asked if you are sure you want to make the adjustment click Yes.

A dialogue box is displayed.

3. Enter the new value by typing it in, clicking the numbers, or clicking << or >> to decrement/increment the

value.

4. Click Enter.

Important: When 963 adjusts a value in a BACnet device it writes the value into the value's priority array.
The value will remain in the array, and be used when it is the highest. Therefore making the adjustment does
not mean that it will be the value that is used. If required the 963's adjustment can be removed from the
array by relinquishing control.