Warner Electric FM Series Foot Mounted Load Cells AC10 Measuring System A-B-C30 User Manual

Page 56

Advertising
background image

56

Warner Electric • 800-825-9050

P-2012-5

3. Apply 24 volt DC electrical power to the

loadcell observing the correct polarity. [Plus
(+) to Pin A and minus (-) to Pin B.] Do not
exceed the maximum rated input voltage.

Note: Allow 20 minutes for the loadcell to
warmup before taking first readings to
insure accurate readings.

4. Measure the output voltage of the LVDT

between the Green and Blue leads for each
tensioncell with a volt meter with a sensitivity
of at least 100,000 ohms per volt. The out-
put voltage should be between 0.5 and 6.5
volts.

5. Since Warner Electric Tensioncells cannot be

mechanically zeroed, refer to the Control
Manual for zeroing out the tare weight volt-
age.

Full Load Adjustment

After the loadcell has been zeroed, a pull test
can be made to check the output voltage of the
loadcell at full load. (See calibration sheet for
voltage output.)

1. Run a non-stretchable rope over the center

of the tension roll simulating the web path.
(Note: The rolls should be free to turn.)

2. With one end of the rope secured, hang a

known weight equally over the roll so that
the total tension is equal to the maximum
strip tension specified on the calibration
sheet, at the other end. (See Figure 10)

3. With a voltmeter connected to Pins C and D

of the connector, an output voltage will be
observed.

4. Repeat Step 3 for the Tensioncell mounted

on the opposite end of the measuring roll.

Warner Electric Ioadcells instrumentation pro-
vides the required signal conditioning and a reli-
able high level output signal for use as feedback
control of a tension drive system. The feedback
signal is directly proportional to the strip tension
applied. If a Warner Electric control is used,
refer to the control manual for further calibration.

Although the electrical output of Warner Electric
tensioncells are sufficient to drive most electrical
indicators, substantial signal conditioning is nor-
mally required for effective tension instrumenta-
tion system control. Refer to the documentation
available from the instrumentation supplier for
more information.

Trouble Shooting

When properly installed in accordance with the
original design specifications Warner Electric
tensioncells should require little or no regular
maintenance or service.

Certain conditions, however, can impair their
inherently accurate and reliable performance.
Therefore, if trouble should arise, the following
conditions should be checked. (Continued on
next page)

Roll

Rope

Web Path

Weights for

Max. Tension

T

T

Figure 10

Advertising