Please pay special attention to the following instructions when connecting the
power cord terminals to the FP unit.
• If the power supply voltage exceeds the FP unit’s specified range, connect a

voltage transformer.

• Between the line and the ground, be sure to use a low noise power supply. If

there is still an excessive amount of noise, connect a noise reducing
transformer.

• Input and Output signal lines must be separated from the power control cables

for operational circuits.

• The FP unit’s power supply cord should not be bundled with or kept close to

main circuit lines (high voltage, high current), or input/output signal lines.

• Connect a surge absorber to handle power surges.
• To reduce noise, make the power cord as short as possible.
• The temperature rating of field installed conductors: 75 ºC only (FP3500-T41-

24V/FP3600-T41-24V only).

When attaching a wire to the FP unit’s rear face FG terminal, (on the AC
Connector), be sure to create an exclusive ground.
(Use a grounding resistance of 100

Ω, a wire of 2mm

2

or thicker, or your country’s

applicable standard.)

• All FP Input and Output signal lines must be separated from all operating

circuit (power) cables.

• If this is not possible, use a shielded cable and ground the shield.

„ OSD Functions

You can operate the FP screen menus via the touch panel, and even if FP is
operating, adjust screen image display to a minute level. The feature is called
OSD (On Screen Display). The items that can be set with OSD and the functions
are shown.

8

Power Supply Cautions

9

Grounding Caution

10

Input/Output Signal Line Cautions

11

Calibration of OSD Display Position

Example of OSD screen

"Ver.*.**" indicates the version of the OSD.

Advertising
This manual is related to the following products: