4.4 Connection of DYC Signal

Cable

The remote type signal cable is shown in Figure 4.3
and Figure 4.4, and the terminal is shown in Figure
4.5.
The maximum cable length is 30 m (97.5 feet).
Remove terminal box cover and wiring connection
dust-cap before wiring.
For remote type the converter has two electrical
connections (cable inlets). Use the left connection
as viewed from the terminal box for the DYC signal
cable and the right connection for the transmission
cable.
If a signal cable kit is supplied by YOKOGAWA,
both ends of the cable must be fi nished in
accordance with the following instructions. Refer to
Section 4.5 “End Processing Method of DYC Signal
Cable“.

CAUTION

After completing the signal cable connections,
install the shielded cover to signal cable terminal
as shown in Figure 4.6.

Unit : mm

F0403.ai

C

(Black)

B

(White)

A

(Red)

A

(Red)

B

(White)

C

(Black)

(Blue)

Specified

Length (L)

30m (max.)

DYC

Flowmeter

Converter

80

70

70

80

60

25

95

60

20

50

50

T

(Yellow)

T

(Yellow)

T: Only for / MV

Figure 4.3

DYC Signal Cable

A (Red)

T

(Yellow)

B (White)
C (Black)

(Red) A

(Yellow) T

(White) B

(Black) C

Outer shield

Inner shield

To Converter

To Flowmeter

F0404.ai

T

: Only for / MV

(Bule)

Figure 4.4

Construction of DYC Signal Cable

Detector (DY-N.../E1)

DYC

T

A

B

C

C

B

A

T

T

A

B

C

Flowmeter(DY-N)

Converter(DYA)

T: Only for /MV

F0405.ai

Input Terminal from built-
in temperature sensor
Input Terminals from
vortex detector
Common Terminal

T

A
B

C

Figure 4.5

Terminal of Detector and Converter

F0406.ai

Vortex Flow Converter

Shield Cover

Signal Cable(DYC)

Power Cable

Figure 4.6

Shielded Cover

Advertising