Operation via hart configuration tool (hart 7), 1 hart protocol revision, 3 setting parameters using dtm – Yokogawa digitalYEWFLO (DY) User Manual

Page 73: Operation via hart configuration tool (hart 7) -1, Hart protocol revision -1, 2 hart, Setting parameters using dtm -1, Important

Advertising
background image

<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>

9-1

IM 01F06A00-01EN

9.

OPERATION VIA HART

CONFIGURATION TOOL (HART 7)

NOTE

In this User’s Manual, HART protocol revision
5 and 7 are described as HART 5 and HART 7
respectively.

Note: HART is a registered trademark of the HART

Communication Foundation (HCF).

9.1 HART Protocol Revision

For the models with the output signal code “-J”,
HART protocol revision 5 or 7 is selectable. The
protocol revision is set as specifi ed in the order.

• Confi rmation by the name plate

The HART protocol revision is shown by the last
number of the serial number.

XXX

F0901.ai

5: HART 5

7: HART 7

In the case of the communication code "-J"

The HART protocol revision is shown by the last number of

the serial number.

XXXXXXXXX XXX

XXXXXXXXX XXX

Figure 9.1 Name Plate

9.2 HART

Confi guration Tool

and Matching of Device
Revision

Before using the HART Confi guration Tool (such
as FieldMate), confi rm that the DD (Device
Description) of the digitalYEWFLO is installed in the
Confi guration Tool before using.

DY and DYA HART 7;

Device type: 0x370B, Device revision: 10

IMPORTANT

Protocol revision supported by HART
confi guration tool must be the same or higher
than that of the device.

Protocol Rev. supported by

HART confi guration tool

5

7

DY or DYA HART 5

Available

Available

DY or DYA HART 7

Not available

Available

The DD revisions for digitalYEWFLO and
Confi guration Tool’s can confi rm in accordance with
the following steps.
If the correct DD is not installed in the HART
Confi guration Tool, download them from the offi cial
HART programming sites, otherwise, contact the
respective vendors of the Confi guration Tool for its
upgrade information.
1. Confi rmation of the device revision for

digitalYEWFLO

• Procedure to callup the fi eld device revision;
[Root Menu]

→ Review → Review1

• ‘Fld dev rev’ in the Review1 shows the revision

number of correspondent fi eld device.

2. Confi rmation of the device revision for the HART

Confi guration Tool

(1) Confi rm the installed DD revision in

accordance with the procedure of the
Confi guration Tool. Refer to its manual how
to confi rm it in detail.

The fi rst 2 digits of the DD fi le are

expressed the device revision, and its last 2
digits are expressed the DD revision.

01 01.XXX

DD revision
Device revision

F0902.ai

9.3 Setting Parameters using

DTM

When confi gure the parameters using FieldMate,
use the DTM (Device Type Manager) reffering to
the following table.

DTM Name

Device Type

Device Revision

DYF HART 7 DTM

0 x 370B

10

Advertising