<6. PARAMETERS>

6-11

IM 01F06A00-01EN

6.4 Parameters

Description

(1) Item A : Display

These items are for the indication of fl owrate and
total.

[A10:FLOW RATE(%)] Flow rate

Flowrate is displayed by “%” to span value.

[A20:FLOW RATE] Flow rate (Engineering
unit)

Flowrate is displayed by engineering unit.

[A30:TOTAL] Total value

Total value of fl owrate is displayed
Note: There will be linked to the value of B45

TOTAL RATE, it is displayed “E” shows
multipiler 10.

Example

B45

A30

10000 (= 10

4

)

999999E4

10 (= 10

1

)

999999E1

0.00001

9.99999

The following item should be done in case
of which Option code /MV is selected and
analog output is “Temperature”.

[A40:TEMP(%)] Temperature value

The measured temperature value is displayed by
“%” to span value of temperature.

The following item should be done in case
of which Option code /MV is selected.

[A41:TEMPERATURE] Temperature value

The measured temperature value is displayed by
engineering unit.

(2) Item B : Easy Setting

These items are for the Principal items to operate
digitalYEWFLO.
A value in “( )” is the data corresponding to indicator.

[B10:FLOW SPAN] Flowrate span

Set the required span with a numerical.

NOTE

The range of measurable fl ow velocity is as
described in Table 13.6

[B15:DAMPING] Damping time constant

Set damping time constant values from 0s to 99sec.

[B20:CONTACT OUT] Contact output

Select contact output.

Item

Description

OFF (0)

------------------------

SCALED PULSE

(1) Scaled pulse output: Refer to “B21”

UNSCALED PULSE (2) Unscaled pulse output: Refer to “B21”
FREQUENCY

(3) Frequency output: Refer to “B22”

ALARM

(4) Alarm output: The status goes

from close to open (OFF) during
alarming.
Refer to Section 6.5 “Self-
Diagnostic (Error Code List)”.

FLOW SW (LOW:ON) (5) Status output: Refer to “B23”
FLOW SW (LOW:OFF) (6) Status output: Refer to “B23”

[B21:PULSE RATE] Pulse output rate

Set output rate in a selection of SCALED PULSE or
UNSCALED PULSE.
SCALED PULSE OUTPUT:
When SCALED PULSE is selected in B20, set
fl owrate per one pulse output. Rate unit is linking to
the fl ow unit.
UNSCALED PULSE OUTPUT:
When UNSCALED PULSE is selected in B20, it
outputs the pulse calculated by following formula.
The formula for output pulse number is as follows.
Output pulse number per one second = vortex
number per one second / PULSE RATE set
number.
Refer to Subsection 10.1.5 “Setting of Pulse Output
(Scaling)”.