2 signatures and relevant parameters, Signatures and relevant parameters -3 – Yokogawa YVP110 User Manual

Page 107

Advertising
background image

<19. Diagnostics>

19-3

IM 21B04C01-01E

19.3.2 Signatures and Relevant

Parameters

The following describes each signature and the

relevant parameters.

(1) Standard Actuator Signature *

1

The standard signature is the fundamental input-to-

position characteristics of the valve, measured at

10% through 90% of the full stroke in 10% intervals

over a round trip.

• The following can be set in a setting parameter

STD_ACT_SIGN_SET:

Recommended Scan Time [seconds]

Scan Time [seconds]

Deviation Margin [%]

• Performing measurement sets the pressure

data in SIGN_DATA_X and the position data

(%) in SIGN_DATA_Y.

• This signature can be saved to non-volatile

memory within the YVP110. To do so, Select

“2” (Save as a Factory data) or “3” (Save

as record data) in SIGN_ DATA_SAVE and

execute saving. The standard signature

previously saved is then overwritten.

It is recommended to save the signature data

taken at the installation as a “Factory data” and

that of the latest measurement as a “Record

data.”

(2) Extended Actuator Signature *

1

The extended actuator signature is the input-to-

position characteristics of the valve, measured at

arbitrary positions within the full stroke of the valve.

As the positions of measuring, 50 points can be

specified for each direction of the valve actions,

totaling 100 points.

• The following can be set in a setting parameter

EXT_ACT_SIGN_SET:

Lower Setpoint [%]

(point to start the measurement)

Upper Setpoint [%]

(point to finish the measurement)

Recommended Scan Time [seconds]

Scan Time [seconds]

Deviation Margin [%]

Sampling Rate [milliseconds]

(not used in this function)

• Performing measurement sets the pressure

data in SIGN_DATA_X and the position data

(%) in SIGN_DATA_Y.

(3) High Resolution Actuator Signature *

1

The high-resolution actuator signature is the input-

to-position characteristics of the valve, measured

with high resolution while sampling data at the

specified time rate. Up to 100 data values can be

stored in the memory of the YVP100. After this limit

is reached during measurement, the stored data will

be overwritten from the leading data in order. Using

ValveNavi, users can continue measurement while

uploading the measured data.

• The following can be set in a setting parameter

EXT_ACT_SIGN_SET:

Lower Setpoint [%]

(point to start the measurement)

Upper Setpoint [%]

(point to finish the measurement)

Recommended Scan Time [seconds]

(not used in this function)

Scan Time [seconds]

Deviation Margin [%]

Sampling Rate [milliseconds]

The sampling rate can be set within the range

of 200 through 1000 milliseconds. The total

number of measured samples can be obtained

by the following formula:

Scan time / sampling rate × 1000 [points]

• Performing measurement sets the pressure

data in SIGN_DATA_X and the position data

(%) in SIGN_DATA_Y.

(4) Step Response Test
The step response test measures time-series

changes in the valve position in response to

a sudden change (step) in the setpoint of the

positioner from the preset initial setpoint to the

destination setpoint.

• The following can be set in a setting parameter

STEP_RESP_SET:

Initial Setpoint [%]

Destination Setpoint [%]

Sampling Rate [milliseconds]

Number of Samples [points]

The sampling rate can be set within the range

of 20 through 1000 milliseconds (corresponding

to the measurement period of 0.4 through 600

seconds). The number of samples can be set

to up to 600.

• Performing measurement sets the positioner

setpoints in SIGN_DATA_X and the position

data (%) in SIGN_DATA_Y.

Advertising