<15. OS Function Block>

15-2

IM 21B04C01-01E

When this action is enabled, the value set in

HYSTVAL serves as hysteresis, which affects the

output as follows:

When SP has increased beyond X12, OUT_1 is

set to Y11.

Then, after SP has decreased below X12 minus

HYSTVAL, OUT_1 returns to follow the set

characteristic.

F1504.ai

(X11, Y11)

OUT_1

(X12, Y12)

SP

HYSTVAL

LOCKVAL=No Lock

LOCKVAL=Lock

Figure 15.4 LOCKVAL and HYSTVAL

When both downstream blocks of the OS block

are ready for cascade connection, the OS block

connects the block on the side of OUT_1 first. For

bumpless mode change on the side of OUT_2,

the balancing time for connection can be set in

BAL_TIME. When either downstream block alone

is ready for cascade connection, the OS block

connects it and enters the Cas mode. When

neither downstream block is ready for cascade

connection, the mode of the OS block is set to

IMan.

15.4 Backward Path

(BKCAL_OUT)

The value of SP or a value calculated from the

value of either BKCAL_IN_1 or BKCAL_IN_2,

depending on the handshake status with the

downstream blocks, is output through BKCAL_

OUT. In normal operating conditions (i.e., BLK_

MODE.actual is Cas or Auto), BKCAL_OUT is set to

the value of SP.

15.5 STATUS_OPTS

STATUS_OPTS is a parameter that stipulates

options about the block’s signal processing and

mode transitions. Table 15.1 shows the options

available in STATUS_OPTS of the OS block.

Table 15.1

STATUS_OPTS of OS Block

Bit

Meaning

Description

1 IFS if BAD

CAS_IN

If this option is True, then: Set

the sub-status components

of OUT_1.status and OUT_

2.status to Initial Fault State

(IFS) if CAS_IN.status is Bad.

4 Propagate Fault

Backward

If this option is True, then: Set

the status of BKCAL_OUT to

device failure if the quality and

substatus components of both

BKCAL_IN_1 and BKCAL_IN_

2 are Bad-Sensor Failure and

Device Failure, respectively.

If this option is False, then: Set

the status of BKCAL_OUT to

device failure if the quality and

substatus components of either

or both BKCAL_IN_1 and

BKCAL_IN_2 are Bad-Sensor

Failure and Device Failure,

respectively.

15.6 Alarm Processing

When the condition shown in the table below is

met in the OS block, the OS block changes the

bit statuses of BLOCK_ERR accordingly and

generates a block alarm (BLOCK_ALM).

Table 15.2

BLOCK_ERR in OS Block

Bit Name of Error

Represented

Description

1 Block

Configuration

Error

The settings of IN_ARRAY

and OUT_ARRAY satisfy

one or more of the following

conditions:

X21 < X11

X12 ≤ X11

X22 ≤ X21

15 Out of Service

The target mode (MODE_BLK.

target) is OS.