20. Troubleshooting

20.1 What to Do First

When a problem occurs, check the following first.
Mounting of YVP110 Positioner

• Is the linkage to the valve actuator correctly set

up?

• Is the feedback lever correctly attached?

• Is the span of rotation angle of the position

sensor against the valve stroke more than the

minimum requirement?

• Has auto tuning been performed after

installation?

Air Piping

• Are the air pipes correctly connected? Is there

no leak of air?

• Is the air supply pressure high enough to drive

the valve?

• Is the A/M selector on the positioner set to A

(automatic)?

Wiring

• Is the YVP110 positioner correctly connected to

the fieldbus?

• Are the conductors incorrectly connected,

in other words, is the plus side connected to

minus, and vice-versa?

• Has the power to the fieldbus been turned on?

Is the terminal-to-terminal voltage equal to or

greater than 9 V?

• Is the terminator correctly installed?

• Is a host system connected to the fieldbus?

20.2 Troubleshooting Communications

Problem

Presumed Cause

Remedy

Ref. Section

Communication with

the YVP110 cannot be

performed.

Wiring is incorrect.

Correct wiring.

4.3, 8.4

The power is off or the power

supply voltage is less than 9 V.

Supply proper voltage.

4.3, Chapter 7

The address detection range is

not correctly set.

Correct address detection range.

9.4

Communication with the

YVP110 is frequently cut off.

The fieldbus is experiencing a

large amount of noise.

Using an oscilloscope or the

like, check the waveform on the

fieldbus.

The YVP110 can be

detected, but neither function

blocks nor transducer block

can be seen.

The node address of the YVP110

is left as the default (0xF8-0xFB).

Change it to an operable address.

See the descriptions for address

settings.

9.4

20.3 Troubleshooting Function Block Parameters

Problem

Presumed Cause

Remedy

Ref. Section

A value cannot be written to a

parameter in the YVP110.

You have attempted to write a

value outside the valid range.

Check the setting range of

parameters.

Appendix 1

The target mode does not allow

write access.

Change the target mode. See the

parameter lists.

Appendix 1

The actual mode of a

function block cannot be

equalized to the target mode.

O/S is set for the target mode of

the resource block.

Change the target mode of the

resource block to Auto.

Appendix 1, 10.1

The I/O of the function block

in question is not connected to

another function block.

Using a configuration tool, set the

virtual communication relationship

(VCR) and link object.

Chapter 9

Schedules that define when

function blocks execute are not

set correctly.

Set the schedules using a

configuration tool.

Chapter 9

The transducer block is in O/S

mode.

Change the target mode of the

transducer block to Auto.

Appendix 1, 10.1

A block’s dynamic

parameters do not update.

The block in question is in O/S

mode.

Change the target mode as

necessary.

Appendix 1, 10.1

O/S is set for the target mode of

the resource block.

Change the target mode of the

resource block to Auto.

Appendix 1, 10.1