<1. Notes on Handling>

1-3

IM 21B04C01-01E

1.8 EMC Conformity Standards

EN61326-1 Class A, Table 2 (For use in industrial

locations)

CAUTION

This instrument is a Class A product, and it is

designed for use in the industrial environment.

Please use this instrument in the industrial

environment only.

1.9 Installation of Explosion

Protected Type Positioner

CAUTION

To preserve the safety of explosionproof

equipment requires great care during mounting,

wiring and piping. Safety requirements also

place restrictions on maintenance and repair

activities. Please read the following section very

carefully.

1.9.1 FM Certification

A) FM Intrinsically Safe Type
Cautions for FM Intrinsically safe type. (Following

cotents refer “Doc No. IFM017-A12 P.1, 1-1, 2, 2-1,

and 2-2.”)
Note 1. Model YVP110 Advenced Valve Positioner

with optional code /FS15 are applicable for

use in hazardous locations.

• Applicable standard: FM3600, FM3610,

FM3611, FM3810, ANSI/NEMA250

• Intrinsically safe, with FISCO parameters, for

use in Class I, II, III, Division 1, Groups A, B,

C, D, E, F, G and Class I, Zone 0, AEx ia IIC

• Non-incendive for Class I, Division 2, Groups

A, B, C, D and Class I, Zone 2, Group IIC

• Indoor/Outdoor hazardous locations, NEMA

4X

• Ambient Temperature: –40 to 60°C

Note 2. Electrical Data

Rating 1

For Groups A, B, C, D, E, F and G or Group IIC

Maximum Input Voltage Vmax: 24 V

Maximum Input Current Imax: 250 mA

Maximum Input Power Pmax: 1.2 W

Maximum Internal Capacitance Ci: 1.76 nF

Maximum Internal Inductance Li: 0 µH

or

Rating 2

For Groups A, B, C, D, E, F and G or Group IIC

Maximum Input Voltage Vmax: 17.5 V

Maximum Input Current Imax: 360 mA

Maximum Input Power Pmax: 2.52 W

Maximum Internal Capacitance Ci: 1.76 nF

Maximum Internal Inductance Li: 0 µH

or

Rating 3

For Groups C, D, E, F and G or Group IIB

Maximum Input Voltage Vmax: 17.5 V

Maximum Input Current Imax: 380 mA

Maximum Input Power Pmax: 5.32 W

Maximum Internal Capacitance Ci: 1.76 nF

Maximum Internal Inductance Li: 0 µH
• In the rating 1, the output current of the

barrier must be limited by a resistor “Ra”

such that

Io = Uo/Ra.

• In the rating 2 or 3, the output characteristics

of the barrier must be the type of trapezoid

which are certified as the FISCO model.

• The safety barrier may include a terminator.

• More than one field instruments may be

connected to the power supply line.

Note 3. Installation

• Dust-tight conduit seal must be used

when installed in Class II and Class III

environments.

• Control equipment connected to the

Assoiciated Apparatus must not use or

generate more than 250 Vrms or Vdc.

• Installation should be in accordance with

ANSI/ISA RP12.6 “Installation of Intrinsically

Safe Systems for Hazardous (Classified)

Locations” and the National Electrical Code

(ANSI/NFPA 70) Sections 504 and 505.

• The configuration of Associated Apparatus

must be Factory Mutual Research Approved

under FISCO Concept.

• Associated Apparatus manufacturer’s

installation drawing must be followed when

installing this equipment.

• The YVP series are approved for Class

I, Zone 0, applications. If connecting

AEx[ib] associated Apparatus or AEx ib I.S.

Apparatus to the YVP series the I.S. circuit

is only suitable for Class I, Zone 1, or Class

I, Zone 2, and is not suitable for Class I,

Zone 0, or Class I, Division 1, Hazardous

(Classified) Locations.