<8. About Fieldbus>

8-1

IM 21B04C01-01E

8. About Fieldbus

8.1 Outline

Fieldbus is a bi-directional digital communication

protocol for field devices, which offers an

advancement in implementation technologies for

process control systems and is widely employed by

numerous field devices.
YVP110 employs the specification standardized

by The Fieldbus Foundation, and provides

interoperability between Yokogawa devices and

those produced by other manufacturers. Fieldbus

comes with software consisting of AO function

block, two DI function blocks OS function block, IS

function block, AR function block and optional PID

function block, providing the means to implement a

flexible instrumentation system.
For information on other features, engineering,

design, construction work, startup and maintenance

of Fieldbus, refer to “Fieldbus Technical Information”

(TI 38K3A01-01E).

8.2 Internal Structure of YVP110

The YVP110 contains two virtual field devices

(VFD) that share the following functions.

8.2.1 System/network Management VFD

• Sets node addresses and Physical Device tags

(PD Tag) necessary for communication.

• Controls the execution of function blocks.

• Manages operation parameters and

communication resources (Virtual

Communication Relationship: VCR).

8.2.2 Function Block VFD

(1) Resource block

Manages the information common to each FB

VFD in YVP110.

(2) Transducer block

Located between Hardware I/O(actuator,

sensor) and AO/DI function blocks, pass the

control signal from AO function block to I/P

module to control the valve position.

(3) AO function block

• Accepts a control signal from an upstream

block and pass the signal to Transducer

block.

• Accept a valve position signal from

Transducer block and feedback it to an

upstream block.

(4) DI function block

Receives the discrete signal from Transcducer

blcok and output them.

(5) PID function block(optional)

Offers PID control function.

8.3 Logical Structure of Each

Block

AR Function

IS Function

OS Function

F0801.ai

YVP110

PID Function

DI Function

Function Block VFD

Resource block

DI Function

AO Function

block

Block tag

OUT

Parameters

Transducer

block

Block tag

Parameters

PD tag (Device tag)

Communication

parameters

VCR

Node address

Position feedback signal

Position Sensor

I/P

Module

Control output

Output to other blocks

Input from other blocks

System/network management VFD

Function block

execution schedule

Block tag

Parameters

Figure 8.1

Logical Structure of Each Block

Setting of various parameters, node addresses,

and PD Tags shown in Figure 8.1 is required before

starting operation.

8.4 System Configuration

The following instruments are required for use with

Fieldbus devices:

Advertising