Yokogawa YVP110 User Manual

Page 113

Advertising
background image

<Appendix 1. Function Block Parameters>

A-2

IM 21B04C01-01E

Relative

Index Index

Parameter Name

Default

(factory setting)

Write

Description

16

1016 RESTART

Restart the YVP110 in the selected way.

1: Running

2: Restart Resource

3: Restart with the default settings defined in FF

specifications.*

1

4: Restart CPU

17

1017 FEATURES

Shows supportable optional features of the block.

18

1018 FEATURE_SEL

.

Parameter used to select the optional features of

the resource block

19

1019 CYCLE_TYPE

Scheduled

Bit string indicating cycle types executable for the

resources

Bit 0: Scheduled; to be scheduled

Bit 1: Event driven; to be driven by an event

Bit 2: Manufacturer specified; executable by a

manufacturer-specified unique function

20

1020 CYCLE_SEL

Scheduled

Bit string used to select the cycle type

21

1021 MIN_CYCLE_T

3200 (100ms)

Minimum execution cycle

22

1022 MEMORY_SIZE

0

Memory size allowed for use of function block

configurations in the device; checked before a

download, but not supported by the YVP110.

23

1023 NV_CYCLE_T

0

Cycle of saving the settings of non-volatile

attribute parameters to the EEPROM. 0 is set with

the YVP110, and saving is not cyclically done.

24

1024 FREE_SPACE

0

Shows the free space memory for configurations

as a percent value. YVP110 shows zero which

means the pre-configured resource.

25

1025 FREE_TIME

0

Shows the free time that can be used for

computations by resources but not supported by

the YVP110.

26

1026 SHED_RCAS

640000

Communication time-out setting for

communications with the device from which the

remote cascade setpoint is sent.

27

1027 SHED_ROUT

640000

Communication time-out setting for

communications with the device from which the

remote output setting is sent; not used in the

YVP110, however.

28

1028 FAULT_STATE

1

Indicates the fault-state.

29

1029 SET_FSTATE

1

Sets the fault-state.

30

1030 CLR_FSTATE

1

Clears the fault-state.

31

1031 MAX_NOTIFY

3

Maximum number of alerts retained in the device

(YVP110).

32

1032 LIM_NOTIFY

3

Maximum number of alerts to be held by the

device (YVP110); used by the user to restrict the

number of alert notifications to the host to prevent

overflow of alert receptions in the host.

33

1033 CONFIRM_TIM

20000 (ms)

Defines the time to wait for confirmation for an

alert.

34

1034 WRITE_LOCK

Unlocked

Prohibits write access from outside the device to

the settings.

35

1035 UPDATE_EVT

Shows the contents of an update event upon

occurrence.

36

1036 BLOCK_ALM

Shows the contents of an alarm event upon

occurrence.

37

1037 ALARM_SUM

Enable

Shows the alarm summary for all blocks within the

device (YVP110).

38

1038 ACK_OPTION

0xFFFF

Defines the acknowledgment action of each alarm

type. By setting a bit to 1, the corresponding alarm

will behave as acknowledged immediately when

it occurs without receipt of acknowledgment from

the host.

Advertising