App-12

IM 04L41B01-04E

Appendix 3 Differences in Components by Release

Number

The component types and attributes that can be created for custom display screens differ
depending on the DX recorder release number.
Hereinafter, release number 3 will be notated as R3. Release number 4 will be notated
as R4 if the firmware version is earlier than 4.11, and "R4(4.11)" if the firmware version is
4.11.

When displaying R3 screen data under R4 or R4(4.11)

• Component attributes that became available for setting in R4 are set to their defaults.
• [2nd span Lower] and [2nd span Upper] settings of trend and scale components can

now be set up to 1 decimal place.

• When displayed under R4(4.11), the batch name component display is updated every

second.

When displaying R4 screen data under R4(4.11)

• Component attributes that became available for setting in R4(4.11) are set to their

defaults.

• Batch name component displays are updated every second.

When displaying R4 or R4(4.11) screen data under R3

• Components not supported in R3 are not displayed.
• The [Depend ID]’s of components dependent on other components that are not

supported in R3 are set to [None].

• Component attributes not supported in R3 are deleted. The [Vertical display] of

components whose attributes are deleted (Labels, Tag no., Tag comment, Units,
SpanL, and SpanU) is changed to [Horizontal display].

• Component attributes not supported in R3 are ignored. The method of plotting is

changed for components whose attributes are deleted (trend and scale).

• For the trend component’s [2nd span Lower] and [2nd span Upper] attributes, the

number of decimal places is changed to 0, and the number after the decimal point is
rounded.

• For the scale component’s [2nd span Lower] and [2nd span Upper] attributes, the

number of decimal places is changed to 0, and the number after the decimal point is
rounded.

• If not displaying the status area in an R4 screen, it is displayed. Components in the

status area are repositioned.

From the point at which you move the cursor to move a component, components in

the status area move below the status area. When the status area is set to No Display,
the height of components whose height is at the maximum remains the same, and the
component is displayed below the status area.

• When displaying R4(4.11) screen data under R3, the batch name component display

is not updated.

When displaying R4(4.11) screen data under R4

• Component attributes not supported in R4 are ignored. The method of plotting is

changed for components whose attributes are deleted (batch name, communication
input, and Modbus in).

• Batch name component displays are not updated.