Single ended inputs, Differential inputs, Analog inputs converter module – Nematron OptiLogic Series User Manual

Page 13: Analog inputs common ground converter module

Advertising
background image

Optimation, Inc.

(256)883-3050

13

www.optimate.com

OptiLogic Series

Single Ended Inputs

Single ended inputs are all referenced to

the same ground point. In many applications,
single ended inputs produce significant
advantages. Single ended inputs require only
one ground connection and one signal input per
measured value. The result is reduced wiring
costs along with the reduced cost per channel on
the analog input module.

In order to use single ended inputs, the

ground connection must be very good. The
measurement devices must also be capable of
being referenced to a common ground.

Differential Inputs

There are cases when the individual

analog inputs cannot be connected to a common
ground. In those cases, a differential input A/D
converter should be used.

With a differential analog input, both a

positive and negative signal line must be
connected for each signal. The analog input
module then measures the difference between
the positive and negative. The effect of one
channel

’s signal on another channel’s signal

should be as little as possible. That relationship
of the effect on the measured value of one

channel to the value input on a second channel is
called

“common mode”. The higher the

“common mode rejection ratio (CMRR)” the
better.

Analog

inputs

Common

ground

Converter Module

A/D

Converter

Bus

Interface

Analog

inputs

Converter Module

A/D

Converter

Bus

Interface

+

+

+

+

-

-

-

-

Advertising