OptiLogic Series

OL2258 High Speed Pulse Counter

Inputs (all)

4

Card Cage Power
Required

100 mA

Pulse Inputs

2

Status Indicators

Logic side LED

Input signal type

Sinking, sourcing or
differential

Input Impedance

2.0K ohms nominal

Input frequency (on
pulse inputs)

80/160 KHz
maximum

Count value

32 bit signed integer

Min. Input On Voltage
(or differential)

4.00V

Frequency data

16 bit signed integer

(Configurable for 1
second or 200 mS count)

Max. Input Off Voltage
(or differential)

3.00V

Counting Modes

Pulse & Direction

Up/Down Count

Quadrature

Max. Input voltage

28V

Outputs

2

Max terminal wire
gauge

18 AWG (use copper
conductors)

Output Type

Open collector

Terminal Strip

Plug In (removable)

Max Output current

300 mA

Terminal Screws

Slotted (0.1

” blade max.)

Output Voltage range

0 - 40VDC

Required Temperature
rating of field installed
conductors

60

C/75C

Weight

1.24 oz (35g)

Terminal block torque

2.2 lb-in

Type

82

Subtype

1

The OptiLogic OL2258 High Speed Pulse Counter module provides for direct pulse

counting for a variety of high speed pulse interface applications. Typical applications include
motion control, metering and velocity measurement. The OL2258 contains on board intelligence
necessary for processing and counting pulse information as well as automatically triggering control
outputs.

The OL2258 can be configured configured to operate in one of three pulse counting modes.

These modes are 1) Pulse & Direction, 2)Up/Down Count and 3) Quadrature . Pulse & Direction
and Up/Down count will operate at up to 80KHz input pulse rates. Quadrature inputs count each
quadrature state transitions at up to 160 KHz. Additionally, the OL2258 will return frequency
information.