Ol2418 analog current input module – Nematron OptiLogic Series User Manual

Page 30

Advertising
background image

Optimation, Inc.

(256)883-3050

30

www.optimate.com

OptiLogic Series

OL2418 Analog Current Input Module

Inputs

8

Card Cage Power
Required

700mA

Input Type

4 - 20 mA

Conversion Type

Successive
approximation

Resolution

14 bit (1 in 16384)

Full Scale Calibration
Error

+/- 15 counts max.
+/- 5 counts typical

Input Impedence

250 ohm +/- 0.05%

Offset Calibration Error

+/- 2 counts max.

Power Isolation

Transformer

Signal Isolation

Optical

Max. Terminal Wire
Gauge

18 AWG (use copper
conductors)

Linearity error

+/- 1.25 counts

Terminal Strip

Plug In (removable)

Input Stability

+/- 2 counts

Terminal Screws

Slotted (0.1

” blade max.)

Terminal block
torque

2.2 lb-in

Required Temperature
rating of field installed
conductors

60

C/75C

Type

18

Subtype

2

Terminal

Terminal

1

Common

6

Channel 4

2

Common

7

Channel 5

3

Channel 1

8

Channel 6

4

Channel 2

9

Channel 7

1

2

4

5

6

7

8

9

10

3

L

O

2418

8 channel

analog

current in

analog current

input module

optical

isolation

To

OptiLogic

processor

4-20 mA

10

9

8

7

6

5

4

3

2

1

4-20 mA

4-20 mA

4-20 mA

4-20 mA

4-20 mA

4-20 mA

4-20 mA

4-20 mA

Advertising