Ol2104 relay output module – Nematron OptiLogic Series User Manual

Page 14

Advertising
background image

www.optimate.com

Terminal

Terminal

1

Out0 NO

5

Out2 NO

2

Out0 C

6

Out2 C

7


OL2104 Relay Output Module

Outputs

4

Card Cage Power
Required

215 mA

Output Type

Mechanical relay

Contact resistance

0.1 ohm (initial)

Contact voltage rating

0 - 24 VDC

0 - 120 VAC

Status Indicators

Logic Side LED

Contact rating

1A (resistive)/point
@24 VDC, 1A/point
@120 VAC, 1A/point

Terminal Strip

Plug In (removable)

Contact type

Form A (SPST)

Terminal Screws

Slotted (0.1î blade
max)

Minimum load

10 mA

Maximum terminal
wire gauge

18 AWG (use copper
conductors)

Contact arrangement

4 isolated normally
open contact relays

Terminal block torque

2.2 lb-in

Mechanical life

10,000,000 operations
per relay (at no load)

Required Temperature
rating of field installed
conductors

60

°C/75°C

Electrical life

100,000 operations per
relay (at full load)

Weight

1.6 oz (58 g)

Type

8

Subtype

1

Inductive load

0

1

Diode protection

O


isolation

L3

8

From

O

ic

ptiLog

2

3

processor

U

O

L

2104

8

7

6

5

4

3

2

1

T

Output module

L2

6

5

L1

4

3

L0

2

1

5-30VDC
5-132VAC

Optimation, Inc.

(256)883-3050

14

Advertising