Ol2408 analog voltage input module – Nematron OptiLogic Series User Manual

Page 29

Advertising
background image

Optimation, Inc.

(256)883-3050

29

www.optimate.com

OptiLogic Series

OL2408 Analog Voltage Input Module

Inputs

8

Power required

700mA

Input Type

0-5 VDC or
0-10VDC

Conversion Type

Successive approximation

Resolution

14 bit (1 in 16384)

Full Scale Calibration
Error

+/- 15 counts max.

+/- 5 counts typical

Input Impedance

10 MOhm

Offset Calibration error

+/- 2 counts max.

Maximum Voltage
Input

+/- 15VDC

Max. Terminal wire
gauge

18 AWG (use copper
conductors)

Linearity error

+/- 1.25 count max

Terminal Strip

Plug In (removable)

Input stability

+/- 2 counts

Terminal Screws

Slotted (0.1

” blade max.)

Terminal block
torque

2.2 lb-in

Required Temperature
rating of field installed
conductors

60

C/75C

Type

17

Subtype

1

1

2

4

5

6

7

8

9

10

3

L

O

2408

Analog

Voltage

Input

10

9

8

7

6

5

4

3

2

1

0-5 VDC

or 0-10 VDC

0-5 VDC

or 0-10 VDC

0-5 VDC

or 0-10 VDC

0-5 VDC

or 0-10 VDC

0-5 VDC

or 0-10 VDC

0-5 VDC

or 0-10 VDC

0-5 VDC

or 0-10 VDC

0-5 VDC

or 0-10 VDC

Terminal

Terminal

1

Common

6

Channel 4

2

Common

7

Channel 5

3

Channel 1

8

Channel 6

4

Channel 2

9

Channel 7

5

Channel 3

10

Channel 8

The OL2408 comes set up for 0-5VDC input range. If you need 0-10VDC input range, you must remove the plastic
module cover by lifting the board latches over the retainer hooks on the PC board. Then, place the jumper on both
pins of J2 and replace the plastic module cover. To change back to 0-5VDC range, repeat the process and remove
the jumper. Having the cover over the range selector jumper ensures that it will not be inadvertantly changed.