Tx rx rx signal gnd signal gnd – Nematron OptiLogic Series User Manual

Page 31

Advertising
background image

Optimation, Inc.

(256)883-3050

31

www.optimate.com

OptiLogic Series

OL2602 Dual RS232 Module

Communication Ports

2

Card Cage Power
Required

110 mA

Type

RS232C

Status Indicators

LEDs for TX and RX

Baud Rates

1200, 2400, 4800,
9600, 19,200
(selectable)

System limitations

*See below

Parity

Even, odd or none

Max. Terminal Wire
gauge

18 AWG (use copper
conductors)

Data bits

7 or 8

Terminal Strip

Plug In (removable)

Transmit buffer

48 bytes

Terminal Screws

Slotted (0.1

” blade

maximum)

Receive buffer

48 bytes

Required Temperature
rating of field installed
conductors

60

C/75C

Weight

1 oz (29g)

Terminal block torque

2.2 lb-in

Type

112

Subtype

1

Terminal (each port)

1

Signal

ground

2

Transmit

3

Receive

* For OL4058 ethernet base a maximum of one OL2602 modules may be used. It must be placed in slot 0. For the

OL4054 ethernet base, a maximum of two OL2602 may be used. They must be placed in slots 0 and 1.

1

1

2

2

3

3

Opti

Logic

Opti

Opti

Opti

Opti

Opti

OL2602

TX
RX
TX
RX

3

3

2

2

1

1

TX

TX

RX

RX

Signal Gnd

Signal Gnd