Brocade VDX 8770-4 Hardware Reference Manual

53-1002563-04

Preparing for the Brocade VDX 8770-4 installation

2

Preparing for the Brocade VDX 8770-4 installation

NOTE

Refer to the safety notices before installation (refer to

“Safety notices”

).

Refer to

“NEBS requirements”

to ensure compliance with NEBS-GR-1089 standards.

Refer to

“Power specifications”

to plan for meeting power supply standards before installing the

chassis.
Refer to

“Environmental requirements”

to plan for your environmental needs.

Refer to

“Managing cables”

to plan for cable management.

DANGER

Installation and removal of the unit must be carried out by qualified personnel only.

The following steps are required to ensure correct installation and operation.

NOTE

Brocade strongly recommends that devices be installed in environments that have minimal dust and
airborne contaminants.

1. Ensure that doorways are wider than 91 cm (36 in.) to accommodate the switch.

2. Provide a space that is 8 rack units (8U) high, 61.19 cm (24.09 in.) deep, and 43.74 cm (17.22

in.) wide. One rack unit is equal to 4.45 cm (1.75 in.). If you are using the VDX 8770-4
Four-Post Flush and Recessed Mount Intake Air Duct Rack Kit, you will need a space that is
10U high to accommodate both the Intake Air Duct Rack Kit and the switch.

Plan to install the Brocade VDX 8770-4 with the port side facing the air-intake aisle. Airflow is
from the left side of the switch to the fan side. If you are using the Intake Air Duct Rack Kit for
mounting the Brocade VDX 8770-4, then the airflow is from the port side to the fan side.

Ensure that the rack is balanced and mechanically secured to provide stability in the event of
an earthquake and that the equipment does not exceed the rack’s weight limits.

3. Ensure that dedicated electrical branch circuits with the following characteristics are available:

Up to four dedicated fused 200–240 VAC, 50–60 Hz feeds or -48 VDC (one per power
supply)

One cable for each power supply

CAUTION

Use a separate branch circuit for each AC power cord, which provides redundancy in case one of
the circuits fails.

Protected by a circuit breaker in accordance with local electrical codes

Supply circuit, line fusing, and wire size adequate to the electrical rating on the switch
nameplate

Location close to the switch and easily accessible