Figure 9, Heat shrink tubing and – Brocade VDX 8770-4 Hardware Reference Manual User Manual
Page 43
Brocade VDX 8770-4 Hardware Reference Manual
23
53-1002563-04
Providing power to the Brocade VDX 8770-4
2
Installed tubing and lugs on power supply wire should conform to
.
FIGURE 9
Heat shrink tubing and lug on DC power supply cable
9. Connect the power lugs to the power supply unit.
Connect the -48V wire to the negative terminal and the 0V wire to the positive terminal.
NOTE
The DC return must be isolated from the chassis ground (DC-I) when making connections to
the power supply.
10. Replace the safety cover.
11. Plug the other end of the cable into the power source.
ATTENTION
Do not connect the switch to the network until the IP addresses are configured.
For information about LED patterns, refer to
Chapter 4, “Monitoring System Components”
1
Heatshrink tubing
2
Power lug