SIMULTANEOUS WELDING AND POWER

Output

Welding Permissible

Permissible

Permissible

Selector Setting

Output

Power Watts

Auxiliary Current in Auxiliary Current in

(Unity Power Factor) Amperes @ 115V * Amperes @ 230V

250

250

NONE

200

200

2500

22

11

160

160

3700

32

16

120

120

5000

44

* *

22

90

90

6000

52

* *

26

45

45

7500

65

* *

32.5

CV LOW

250

5000

43

* *

21.5

60

7500

65

* *

32.5

CV MEDIUM

250

2750

40

* *

20

80

6500

56

* *

28

CV HIGH

250

1200

10

5

100

6000

52

* *

26

A-8

INSTALLATION

RANGER 9

A-8

STANDBY POWER CONNECTIONS

The Ranger 9 is suitable for temporary, standby, or
emergency power using the engine manufacturer

s rec-

ommended maintenance schedule.

The Ranger 9 can be permanently installed as a stand-
by power unit for 230V-3 wire, single phase 40 ampere
service.

(Connections must be made by a licensed electri-
cian who can determine how the 115/230V power
can be adapted to the particular installation and
comply with all applicable electrical codes.) The
following information can be used as a guide by the
electrician for most applications (refer also to the
connection diagram shown )

IMPORTANT :

When the Ranger 9 is connected to a

230 volt, 3-wire line, the unit should be operated with
the idler switch in the

HIGH

idle position to avoid load

sensing problems. If the machine is set for automatic
idle, the 230 volt circuit will sense loads and cause the
engine to accelerate to high idle. However, since only
one line of the circuit senses current, 115 volt power
drawn from only one line to neutral may result in the
engine not going to high idle.

WARNING

Install a double pole, double throw switch between

the power company meter and the premises
disconnect.
Switch rating must be the same or greater than
the customer

s premises disconnect and service

overcurrent protection.

Take necessary steps to assure load is limited to

the capacity of the Ranger 9 by installing a 40 amp
230V double pole circuit breaker. Maximum
rated load for the 230V auxiliary is 40 amperes.
Loading above 40 amperes will reduce output
voltage below the allowable -10% of rated
voltage which may damage appliances or other
motor-driven equipment.

Install a 50 amp 115/230V plug (NEMA type 14-50)
to the Double Pole Circuit Breaker using No. 8, 4
conductor cable of the desired length. See
Accessories Section for (The 50 amp 115/230V
plug kit.)

Plug this cable into the 50 amp 115/230 V

receptacle on the Ranger 9 case front.

* Each duplex receptacle is limited to 20 amps.

* * Not to exceed 35A per 115 VAC branch circuit when splitting the 230 VAC output.