Installation, Warning, A-9 connection of ranger 9 to premises wiring – Lincoln Electric IM753 RANGER 9 User Manual

Page 17

Advertising
background image

A-9

INSTALLATION

RANGER 9

A-9

CONNECTION OF RANGER 9 TO PREMISES WIRING

• Only a licensed, certified, trained electrician should install the machine to a premises or residential

electrical system. Be certain that:

•The installation complies with the National Electrical Code and all other applicable electrical codes.

•The premises is isolated and no feedback into the utility system can occur. Certain state and local

laws require the premises to be isolated before the generator is linked to the premises. Check your
state and local requirements.

•A double pole, double throw transfer switch in conjunction with the properly rated double throw

circuit breaker is connected between the generator power and the utility meter.

WARNING

230 Volt

60 Hz.

3-Wire

Service

POWER

COMPANY

METER

230 VOLT

115 VOLT

115 VOLT

LOAD

N

NEUTRAL
BUS

GROUND

PREMISES

DISCONNECT AND

SERVICE

OVERCURRENT

PROTECTION

GND

N

NOTE: No. 8 COPPER CONDUCTOR CABLE SEE

NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE

SIZE RECOMMENDATIONS.

230 VOLT

GROUNDED CONDUCTOR

35AMP

230 VOLT

DOUBLE

POLE

CIRCUIT

BREAKER

DOUBLE POLE DOUBLE THROW
SWITCH RATING TO BE THE SAME

AS OR GREATER THAN PREMISES

SERVICE OVERCURRENT

PROTECTION.

50 AMP, 115/230

VOLT PLUG

NEMA TYPE 14-50

50 AMP, 115/230 VOLT

RECEPTACLE