Rt‐15 flow monitor, Reset input, Limits/pulse outputs – AW Gear Meters RT-15 User Manual

Page 12: Operation and programming manual, Notice, Reset

Advertising
background image

RT‐15 Flow Monitor

 

Operation and Programming Manual 

 

 

 

11 

      
 

 

1 0 0 O h m

(Em it te r)

(C o lle c to r)

5 0 m A M a x.

LIM IT O UTPUTS

(Iso la te d )

LIM IT (+ )

LIM IT (- )

5 - 3 0 VD C

The RT‐15 is internally isolated from the DC supply by a DC/DC converter. A power‐on LED is provided on 
the connection board and a two Amp mini‐fuse protects the circuitry in case of a supply fault. (See 
drawing below.)  

 

Figure 3: Wiring Connections 

Reset Input 

An opto‐isolated input is used to reset the TOTAL A (Job Total). See TOTAL A RESET on page 21 for 
information regarding resetting the job totalizer. 

 

 

 

Limits/Pulse Outputs 

Two opto‐isolated NPN open‐collector outputs can sink or source depending on connection (i.e., power 
can flow in or out).  

 

Connection polarity: collector (+), emitter (‐). See adjacent 
diagram.  

Output ratings are listed on page 9. You can assign either 
output to a rate limit, total limit for batching, or as a totalizer 
pulsed output. See LIMITS Display Mode on page 25 and LIMITS 

 

RE

S

E

T

+

RE

S

E

T

-

LIM

IT

1

+

LIM

IT

1

-

LIM

IT

2

+

LIM

IT

2

-

L

OOP

-

LO

O

P

+

+V

c

c

E

A

R

T

H G

R

OU

ND

SUP

P

LY

N

E

GA

T

IV

E

1

5

-24

V

/DC

SUP

P

L

Y

W IRIN G TERM IN A LS

(UN D ER REA R C O VER)

2 A M IN I- FUSE

JUL 2005 aw

Z00257 ver 1.2

F2

LE2

LE

1

PO W ER
L ED

m A O UT
LED

C USTO M ER C O N N EC TIO N S

(LEFT TO RIGHT)

1 5 - 2 4 /D C SUPPLY

+ Vd c Su p p ly

SUPPL Y N EGA TIVE

- Vd c Su p p ly

EA RTH GRO UN D

(N o t Us e d , u s e En c l. Gn d Te rm .)

RESET +

O p t ic a lly is o la t e d in p u t (+ )

RESET -

O p t ic a lly is o la t e d in p u t (- )

L IM IT1 +

O p t ic a lly is o la t e d o u t p u t (+ )

L IM IT1 -

O p t ic a lly is o la t e d o u t p u t (- )

L IM IT2 +

O p t ic a lly is o la t e d o u t p u t (+ )

L IM IT2 -

O p t ic a lly is o la t e d o u t p u t (- )

+ Vc c

Su p p ly O u t p u t (sa m e a s D C Su p p ly)

L O O P +

Is o la t e d m A Lo o p (+ )

L O O P -

Is o la t e d m A Lo o p (- )

EN C LO SURE
GRO UN D

TERM IN A L

3 .3 Ko h m

RESET +

5 - 3 0 VD C

RESET IN PUT

(Is o la t e d )

RESET -

+

M o m e n t a ry