RT‐15 Flow Monitor

 

Operation and Programming Manual 

 

 

 

18 

      
 

RATE A Pulse Length (RATE A PL) 

The rate is calculated by the pulse length method based on the SAMPLE A variable. It is displayed based 
on the corresponding KFR factor, decimal location, and engineering units. View the gate time 
measurement RATE A GT by using the SEL button (or magnetic switch) while in the RATE A PL display as 
illustrated below. The rate display reverts to RATE A PL if power is cycled to the RT‐15.  A typical display:  

 

 

 

RATE Mode Programming 

Program the Rate parameters from the RATE A GT or RATE A PL display screen. Also program RATE A PL 
variables from the RATE A GT screen, or vice versa, by toggling to the RATE A PL mode using the SEL 
button (or magnetic switch). Use the MODE/DN button (or magnetic switch) to select the RATE GT 
display.  Press and hold the ENT button or maintain the ENT magnetic switch. The display first shows a P 
in the lower left‐hand corner and then displays the first program variable for that rate display mode. You 
can access three parameters for either mode as follows: 

RATE A 

GT

 

RATE A 

PL

 

 KFR A VALUE 

 KFR A VALUE 

 GATE A B 

 SAMPLE A 

 ENG UNITS A 

 ENG UNITS A 

 

KFR A Value 

Scaling factor to display rate in a desired engineering unit such as GPM. The KFR factor entered here also 
determines the decimal resolution of the rate display. The KFR is calculated using the K‐factor of the 
transducer being monitored. The K‐factor is the number of impulses per engineering unit established by 
the transducer manufacturer or by a calibration test. 

 

 The AW Gear Meters Calibration sheet provides the K‐factor and recommended KFR values. 

 

Initial default is: 100.00 (displays Hertz to two decimal places) 

 

The KFR factor is calculated using the following formula: 