RT‐15 Flow Monitor

 

Operation and Programming Manual 

 

 

 

      
 

KFT 

Scaling for display of total in specific engineering units. Determines display decimal resolution.  

 Initial value=10000.  (pulses with no decimals) 
 KFT = 10000/K‐FACTOR 

where K‐FACTOR is the avg. number of pulses/ eng. unit of the transducer. 

Round result to desired decimal accuracy and enter KFT using only that number of decimal places. Use 
no more than four digits regardless of decimal point position! Maximum = 65535 with the decimal in any 
location.  

ENG UNITS 

The desired engineering units for display of total are programmable using up to four letters.  Example: 
GAL_ 

TOTAL RESET

With the cover removed and outside of a hazardous area use MODE/DN button to view TOTAL, and 
RESET/UP button to reset.  

 

 

GR TOTAL RESET 

With cover open only! Use MODE/DN button and SEL button to view GR TOTAL, press RESET/UP button 
plus ENT button. Use SEL button for “Y”; press ENT to reset and exit. 

Product Description 

The RT‐15 is a meter‐mounted digital flow monitor housed in a hazardous‐location rated enclosure. 
The unit’s large, backlighted LCD display makes it easy to monitor flow rate and total in your choice 
of engineering units. A variety of sensor noses make the RT‐15 compatible with many of the flow 
meters available from AW Gear Meters.   

Access Information and Make Changes 

You can make program or mode changes, or reset the totalizer in two ways. When the faceplate is 
open, enter information using pushbuttons; when the faceplate is closed, use a magnet wand to 
make changes.  

You can also reset the totalizer, and monitor flow rate limits and total output remotely via a 
computer or PLC.  

 

 