Total unit, Analog output scaling, Fixed output source – AW Gear Meters RT-30EX User Manual

Page 21: Rt-30ex flow transmitter

Advertising
background image

RT-30EX Flow Transmitter

Operation and Programming Manual

21

RT-30EX User Manual, Rev. 1.7 02/07/2012

TOTAL unit

Use the

UP

and

DN

buttons to scroll through the available units to scale the TOTAL and GRAND TOTAL

screens.
The available units are:

GAL

(US gallons)

LIT

(Liters)

CC

(Cubic centimeters)

BBL

(Barrels)

ML

(Milliliters)

M3

(Cubic meters)

OZ

(Liquid ounces)

PUL

(Pulses)

The Rate and Total units do not have to be the same. Once the desired unit is showing, pressing

ENT

completes the scaling programming and returns display to the main programming menu.

Analog output scaling

When entering the Analog programming menu, the first screen asks to select the Analog Source, or what
the analog output value is to represent. There are 4 choices as shown in Figure 23.

Using the

UP

and

DN

buttons scrolls through the 4 choices that the mA output can represent: a fixed mA

output value, the input flow rate, the totalizer value or the grand totalizer value. Press

ENT

when

correct choice is showing.

Fixed output source

This option allows the user to select a constant mA value the RT-30EX will output regardless of any
changing values. A constant mA signal could be used as an external indicator showing if the RT-30EX is
on. Allowable values are from 2mA to 20mA.

Select Analog Source

_____________

~Fixed Output
~RATE
~TOTAL
~GRAND TOTAL

UP/DN

ENT

Scaling menu

Source options

Fixed mA output

02.00 mA

EXIT

Figure 23: Analog source selection screen

Figure 24: Fixed mA output programming
screen