Fine ma adjustment, Coarse ma adjustment, Limit & frequency adjustment – AW Gear Meters RT-30EX User Manual

Page 32: Rt-30ex flow transmitter

Advertising
background image

RT-30EX Flow Transmitter

Operation and Programming Manual

32

RT-30EX User Manual, Rev. 1.7 02/07/2012

Fine mA adjustment

When choosing the Fine adjustment option, the screen will appear which shows the active mA output
value. Change this number to any desired value between 2mA and 20mA and when

ENT

button is

pressed, the RT-30EX will output this value. This also returns the screen to the adjustment type screen.
Press

SEL

to see output value again and make new change.

Coarse mA adjustment

When choosing the Coarse adjustment option, the screen will appear where the mA output value can be
changed. When pressing the

UP

button, the screen value (and mA output value) increments by 1mA, to

a max of 20mA. When pressing the

DN

button, the screen value (and mA output value) decrements by

1mA to a min of 2mA. This is the fastest way to test the mA output range if no specific mA output value
is required. Press the

EXIT

button to leave this mode.

Limit & frequency adjustment

The Limit and Frequency outputs can be manually controlled to change states simultaneously using one
of 3 methods. The fine adjustment allows the user to enter a specific frequency to output between 2Hz
to 4,500Hz. The coarse adjustment allows the user to output a frequency and change the rate in 25Hz
increments using the

UP

and

DN

buttons. The ON/OFF adjustment allows the user individually toggle

the output state between on and off using the

UP

,

DN

and

SEL

buttons.

> Fine adjustment

Coarse adjustment

Enter mA value to
output

Output = 04.00 mA

SEL

ENT

Use UP/DN keys to
change output in 1 mA
increments

Output = 04.00 mA

Fine adjustment

> Coarse adjustment

EXIT

SEL

Figure 41: Fine mA output adjustment screens

Figure 42: Coarse mA output adjustment screens