RT-30EX Flow Transmitter

Operation and Programming Manual

22

RT-30EX User Manual, Rev. 1.7 02/07/2012

Zero Flow mA

02.00 mA

Min Flow Rate
00000.00 GPM
Min Flow mA
> 04.00 mA

Max Flow Rate
> 00000.00 GPM
Max Flow mA
20.00 mA

Max Flow Rate
00000.00 GPM
Max Flow mA
> 20.00 mA

Min Flow Rate
> 00000.00 GPM
Min Flow mA
04.00 mA

ENT

ENT

ENT

ENT

EXIT

EXIT

RATE source

RATE source allows the user to configure the mA output to represent the flowrate value. The analog
output span can be scaled for either zero to max flow or a non-zero flow to max flow. If the flow rate
goes above the programmed maximum flow rate, the analog output will continue to increase, up to a
maximum of 22mA. This is useful for system fault detection.

Min Flow Rate

Enter the minimum user flow rate. This can be a non-zero value, such as the lowest application flow
rate if the equipment monitoring the mA signal can be programmed as such. It can also be entered as
zero, but in this case it will affect the accuracy of the mA reading vs flow accuracy. If a non-zero value is
entered, the user will also be asked to enter a mA value to represent zero flow.

Min Flow mA

Enter the mA to represent the above entered minimum flow rate. Value must be equal to or greater
than 2mA.

Max Flow Rate

Enter the maximum flow rate to monitor.

Max Flow mA

Enter the mA value to represent the above entered maximum flow rate value. 20mA is the maximum
allowable value.

Zero Flow mA

This screen only shows if the Min Flow Rate was programmed as a non-zero value. Enter the mA value
to represent zero flow. Lowest value allowable is 2mA and it cannot be greater than the Min Flow mA
value.

Figure 25: Analog Output, RATE source programming screens