I/o manual adjustment, Analog output adjustment, Rt-30ex flow transmitter – AW Gear Meters RT-30EX User Manual

Page 31: Operation and programming manual

Advertising
background image

RT-30EX Flow Transmitter

Operation and Programming Manual

31

RT-30EX User Manual, Rev. 1.7 02/07/2012

I/O Manual Adjustment

Whether for troubleshooting purposes or to manually control external equipment, the RT-30EX allows
the user to enter an I/O routine in which the analog output, Limit outputs and Frequency outputs can be
controlled and the external Reset input can be monitored. A good use of this feature is to verify
communication between the RT-30EX outputs and the users’ readout equipment in a controlled fashion
before final system installation.

When entering the I/O programming mode from the STATUS screen, use the

UP

or

DN

button to change

the I/O Function to ‘Test output’ as shown in Figure 40 above and press

ENT

. Next choose which I/O to

change.

Analog output adjustment

The user can manually control the mA output to any value between 2mA to 20mA in one of two ways.
Fine adjustment allows user to program a specific mA value to output. Coarse adjustment allows user to
increment or decrement the mA value in 1mA steps using the

UP

and

DN

buttons.

I/O Function

> Test output

ENT

Adjust mA output?

NO YES

EXIT

Adjust Limit outputs?

NO YES

EXIT

NO

Monitor Reset input?

NO YES

EXIT

STATUS L1 OFF : L2 OFF
RA 12345.67 HZ
TO 0123456789 PUL
ANLG 20.00 mA

ENT

(hold for 3 seconds)

NO

NO

EXIT

YES

mA

output

menu

Back to

STATUS

screen

EXIT

YES

Limit

Output

menu

Back to

STATUS

screen

EXIT

YES

Reset

Monitor

screen

Back to

STATUS

screen

Figure 40: I/O adjustment top menu