Programming for DACT-UD2

20

DACT-UD2 Communicator PN 53037:B 4/01/08

3.1.1.3 Secondary Phone

Press 3 while viewing On Board DACT Screen #1 to program the type of secondary
phone line being connected to the DACT-UD2. The following screen will be
displayed:

To select the type, press 1 while viewing the Secondary Phone Line screen. The
following screen will be displayed:

Press 1 to select Touchtone dialing, 2 to select Rotary dialing with a make/break
ratio of 67/33 or 3 to select Rotary dialing with a make/break ratio of 62/38.

3.1.1.4 Service Terminal

The MS-9600LS can be programmed remotely from a PC using a modem and
telephone line. Information can also be retrieved from the FACP using the same
method. The Upload/Download option allows an operator to set the necessary
parameters to allow the uploading and downloading of data between the FACP and
PC. The Service Terminal selection provides the means for entering these
parameters.

Pressing 1 while viewing On Board DACT Screen #2 will cause the following
screen to appear:

3.1.1.4.1 Ring Count
The ring count designates the number of rings allowed on the phone line prior to
answering an incoming call from a service terminal. The factory default is 0 which
means the control panel will not answer any incoming calls. This entry may be
programmed for 1 to 25 rings.

To change the Ring Count, press 1 while viewing the Service Terminal Screen #2.

ON BOARD DACT
1=ENABLED
2=PRIMARY PHONE
3=SECONDARY PHONE

On Board DACT Screen #1

ON BOARD DACT

SECONDARY PHONE LINE

1=TYPE TOUCHTONE

Secondary Phone Line Screen

PHONE LINE

1=TOUCHTONE

2=ROTARY 67/33

3=ROTARY 60/40

Secondary Phone Type Screen

ON BOARD DACT
1=SERVICE TERMINAL
2=CENTRAL STATION
3=SUPERV PHONE LINE

On Board DACT Screen #2

SERVICE TERMINAL

1=RING COUNT 0

Service Terminal Screen