Fire-Lite DACT-UD2 Digital Alarm Communicator/Transmitter User Manual

Page 22

Advertising
background image

Programming for DACT-UD2

22

DACT-UD2 Communicator PN 53037:B 4/01/08

3.1.1.5.2 Backup Reporting
The DACT-UD2 can be programmed to transmit reports to primary and/or
secondary central station phone numbers as a backup. Press 2 while viewing
Central Station Screen #1 to display the following screen:

Press 1 to have all reports transmitted to the central station secondary phone number
as a backup only if the primary phone line fails or 2 to send reports to the first
available phone number.

3.1.1.5.3 Trouble Call Limit (Dialer Runaway Prevention)
The Call Limit option limits the number of DACT-UD2 trouble calls to the Central
Station, to a programmed amount between 0 and 99, for each unique trouble within
a 24 hour period. Separate limit counters keep track of each unique type of trouble.
Note that the number of phone line (communication) faults called to the Central
Station are not limited by this feature. No subsequent restoral message is sent to the
Central Station(s) for a particular trouble whose call limit has been reached. Local
DACT-UD2 annunciation will still track the particular trouble and restoral.

To set the Trouble Call Limit, press 3 while viewing Central Station Screen #1. The
following screen will be displayed.

Enter a value between 00 and 99, then press Enter to set the Call Limit to this value.

Note: Entering a value of 00 will disable the Trouble Call Limit allowing the
DACT-UD2 to call the Central Station an unlimited number of times. This is the
factory default setting.

BACKUP REPORTING

1=BACKUP ONLY

2=FIRST AVAILABLE

Backup Reporting Screen

TROUBLE CALL LIMIT


00-99 RANGE

*

Backup Reporting Screen

Advertising