Section 1 product description, 1 product features, 2 compatible panel – Fire-Lite DACT-UD2 Digital Alarm Communicator/Transmitter User Manual

Page 8: 3 specifications, Product description

Advertising
background image

Product Description

8

DACT-UD2 Communicator PN 53037:B 4/01/08

SECTION 1

Product Description

The DACT-UD2 (Digital Alarm Communicator/Transmitter) transmits system status to
UL listed Central Station Receivers via the public switched telephone network. The
communicator mounts to the FACP main circuit board inside the panel cabinet and is
capable of reporting 636 points or 99 zones. The DACT-UD2 is supplied standard with
the MS-9600UDLS/E and is optional for the MS-9600LS/E.

1.1 Product Features

Dual supervised telephone lines

Mounts inside the control panel

Extensive transient protection

Communicates vital system status including:

 Independent zone/point alarm
 Independent zone/point trouble
 Independent zone/point supervisory
 AC power loss
 Low/No battery
 Battery charger trouble
 Earth fault
 System off normal
 12 or 24 hour test signal with alternating phone lines
 Abnormal test signal
 Annunciation at control panel of DACT troubles including loss of phone lines,

communication failure with either Central Station, total communication failure

 NAC faults
 SLC faults
 Annunciator/option faults

1.2 Compatible Panel

The DACT-UD2 has been designed to be compatible with the following control panel:

MS-9600LS

MS-9600UDLS

1.3 Specifications

DC Power - J1 Connector

Current draw in standby and alarm:

U Standby = 0.0193 amps max.
U Alarm = 0.0335 amps max. (communicating)

Advertising