Programming for DACT-UD2

DACT-UD2 Communicator PN 53037:B 4/01/08

27

Ademco Contact ID & SIA Formats

The information shown in Table 3.1 is automatically programmed for the Central
Station phone number Event Codes when the Ademco Contact ID or SIA Format is
selected. Enter 0s for an Event Code Setting to disable the report.

Table 3.1 Event Codes

Event Description

Ademco Contact ID

SIA

Active

Active

Restoral

PULL STATION

115

FA

FH

MON-USER-DEF-1

115

FA

FH

WATERFLOW

113

SA

SH

MON-USER-DEF-2

113

SA

SH

SMOKE (PHOTO)

111

FA

FH

DET-USER-DEF-1

111

FA

FH

SMOKE (ION)

111

FA

FH

DET-USER-DEF-2

111

FA

FH

HEAT DETECT

114

KA

KH

DET-USER-DEF-3

114

KA

KH

SMOKE DUCT-P

116

FA

FH

DET-USER-DEF-4

116

FA

FH

PHOTO W/HEAT

111

FA

FH

DET-USER-DEF-5

111

FA

FH

DUCT SUPERVISORY

200

FS

FV

DET-USER-DEF-6

200

FS

FV

PHOTO SUPERV

200

FS

FV

DET-USER-DEF-7

200

FS

FV

PHOTO ADAPT

111

FA

FH

DET-USER-DEF-8

111

FA

FH

PHOTO BEAM

111

FA

FH

DET-USER-DEF-9

111

FA

FH

not used

000

00

00

not used

000

00

00

not used

000

00

00

not used

000

00

00

not used

000

00

00

not used

000

00

00

not used

000

00

00

not used

000

00

00

not used

000

00

00

not used

000

00

00

MONITOR

110

FA

FH

MON-USER-DEF-3

110

FA

FH

not used

000

00

00

not used

000

00

00

SMOKE CONVEN

111

FA

FH

MON-USER-DEF-5

111

FA

FH

HEAT CONVENTIONAL

114

KA

KH

MON-USER-DEF-6

114

KA

KH

MEDIC ALERT

100

MA

MH

MON-USER-DEF-7

100

MA

MH

HAZARD ALERT

150

PA

PH

MON-USER-DEF-8

150

PA

PH

TORNADO ALRT

150

PA

PH

MON-USER-DEF-9

150

PA

PH

not used

000

00

00

not used

000

00

00

TAMPER

144

TA

TH

MON-USER-DEF-11

144

TA

TH

MON SUPERVISORY

200

FS

FV

MON-USER-DEF-12

200

FS

FV