FCPS-24FS Series Instruction Manual — P/N 51883-L8:J1 8/30/13

13

General

System Overview

can be used as a door holder circuit which will provide a steady 24 VDC output until an alarm con-
dition or AC fail condition causes it to drop to 0 VDC following a 10 second delay. All four out-
puts can also provide power.

One possible application for the FCPS remote power supply utilizes the NAC repeater feature. In
this application, one or two NACs are connected from the main FACP to the remote power supply
control input circuits. When the control input circuits are activated by the reverse polarity of the
NACs, the power supply will activate its corresponding output circuits as programmed by SW1
DIP switch configuration (refer to Table 3.1 on page 20).

During the inactive state, the remote power supply supervises its NAC field wiring for short and
open conditions. If a fault is detected, the power supply will enter a trouble condition and illumi-
nate the NAC Trouble LED. When the NACs are activated, the supervision is disabled and the cir-
cuits are no longer supervised (except for short circuit conditions). Supervision of other power
supply faults such as low battery, battery charger trouble, ground fault and AC loss will continue
and may be monitored via the power supply trouble relay.

If an application requires that all four outputs activate at the same time, only one NAC is required
from the FACP. For this application, the NAC is connected to control input circuit #1 and SW1
DIP switch is set for this operation.

Style Y NAC

or Door

Holder Power

Output #4

AC Power

Figure 1.2 Simplified FCPS Block Diagram

Battery Charger

Style Y NAC

Output #3

Style Y NAC

Output #2

Style Y NAC

Output #1

Note: All NAC
outputs can be
converted to Style Z
with a ZNAC-4
option module

FCPS Trouble

Contact Output

24 VDC Specific
Application Power

NAC Control
Input #2
(from FACP)

NAC Control
Input #1
(from FACP)

Sync. Input

Input/Output Functions are Programmable

by SW1 DIP Switch Settings