Auxiliary power control, 5 charger enable/disable, 6 door closers – Fire-Lite FCPS Series Field Charger/Power Supply User Manual

Page 23: Charger enable/disable 3.2.6: door closers

Advertising
background image

FCPS-24FS Series Instruction Manual — P/N 51883-L8:J1 8/30/13

23

Programmable Features Description

Programming Options

Auxiliary Power Control

The 24 VDC Auxiliary power from TB4 Terminals 9(+) & 10(-) can be resettable or nonresettable
power only when the power supply is configured for General Alarm operation. For all other con-
figurations, the auxiliary power output is only nonresettable.

In the General Alarm configuration, the Auxiliary power output can be made resettable by applying
a steady signal to Control Input 2 (positive 12 to 24 VDC on TB4 Terminal 7 and common on Ter-
minal 8). Temporarily removing the voltage or reversing the polarity will cause the Auxiliary
power output to reset for 6 seconds.

3.2.5 Charger Enable/Disable

The FCPS-FS battery charger can be disabled to accommodate an external battery charger. Setting
DIP switch 7 to the default setting of OFF will enable the battery charger. Setting DIP switch 7 to
the ON position will disable the charger. It should only be disabled if an external battery charger is
being used for the FCPS-FS.

3.2.6 Door Closers

Output Circuit #4 can be configured as an NAC or door closer circuit. Setting DIP switch 8 to the
OFF position will configure Output Circuit #4 as an NAC. Setting DIP switch 8 to the ON position
will configure only Output Circuit #4 as a door closer circuit which will provide a steady 24 VDC
to door holders until an alarm or AC fail condition removes the power following a 10 second delay.

ON

OFF

Split Temporal

• FCPS configured as Master (switch 3 OFF), Control Input #1 controls NAC Outputs 1 & 2

and Control Input #2 controls Outputs 3 & 4

1

which will generate a Temporal code signal

without sync; Sync Input is ignored.

• FCPS configured as Slave (switch 3 ON), Control Input #1 controls NAC Outputs 1 & 2 and

Control Input #2 controls Outputs 3 & 4

1

which will generate a Temporal code signal without

sync; Sync Input is monitored for Outputs 1 & 2

2

.

• Only nonresettable Auxiliary Power is available from TB4 Terminals 9 & 10.

ON

ON

Selective Silence

4

• FCPS configured as Master (switch 3 OFF), NAC Outputs 1 through 4

1

are controlled by

Control Input #1; Sync Input is ignored.

• Control Input #2 determines when Selective Silence for all outputs will occur.
• Only nonresettable Auxiliary Power is available from TB4 Terminals 9 & 10

1 If Door Closer function is selected (switch 8 ON), Output 4 does not function as an NAC, therefore sync input is

ignored for Output 4.

2 If no synchronization is selected by switches 1 & 2, the Sync Input is ignored.
3 When using Split Alarm with power supply configured for Slave Mode, System Sensor cannot be used (use

System Sensor with Master Mode only).

4 Selective Silence allows the silencing of the sounder portion of a horn/strobe combination device without turning

off the strobe.

Table 3.3 Input/Output Configurations

Advertising