Section 5: applications – Fire-Lite FCPS Series Field Charger/Power Supply User Manual

Page 27

Advertising
background image

FCPS-24FS Series Instruction Manual — P/N 51883-L8:J1 8/30/13

27

Section 5: Applications

5.1 Controlling Four NACs With One Input and Selective

Silence

In this application, the power supply has been set as a master with synchronized outputs and selec-
tive silence (see SW1 switch settings in following illustration). All four FCPS-24FS output circuits,
which are shown as NACs (Notification Appliance Circuits), can be controlled from one input such
as an addressable control module as illustrated in Figure 5.1. The control module can be powered
from the FCPS-24FS auxiliary 24 VDC power output (TB4, Terminals 9 & 10) and supervised by
an EOL relay. An addressable relay module, programmed as an alarm output and a silenceable
point,
can be used as a selective silence input.

NOTE: The Relay Module is required only for this application with the power supply set as Master.
If the power supply is set as Slave, the Relay Module is not required. In Slave mode, selective
silence (horn mute) is provided by the FACP through the sync input.

NOTE: Mass Notification (MN) only, Fire only, or MN/Fire combo NACs only are
allowed.