NEC Power-limited (Class 2) Wiring Requirements

2.4 NEC Power-limited (Class 2) Wiring Requirements

Power-limited (Class 2) and nonpower-limited circuit wiring must remain separated in the cabinet.
All power-limited (Class 2) circuit wiring must remain at least 0.25” away from any nonpower-lim-
ited circuit wiring. Furthermore, all power-limited (Class 2) circuit wiring and nonpower-limited
circuit wiring must enter and exit the cabinet through different conduits. One such example of this
is shown below. Your specific application may require different conduit knockouts to be used. Any
conduit knockouts may be used. For power-limited (Class 2) applications, use of conduit is
optional.

Figure 2.5 Power-limited (Class 2) Wiring Example

AC Power
Nonpower-limited

Output Circuits
Power-limited Circuits (Class 2)

Relay Contacts
Nonpower-limited Circuit

Input Circuits
Power-limited Circuit
(Class 2)

Specific Application
Power & SLC are
Power-limited Circuits
(Class 2)

24

fspw

rltpH

.w

m

f

*If the SLC device does

not match the one in this

figure, refer to the SLC

manual wiring conver-

sion charts for legacy

and newer versions of

the modules.