FCPS-24FS Series Instruction Manual — P/N 51883-L8:J1 8/30/13

Power Supply Requirements

Calculating the System Current Draw

Table 6.3 contains three columns for calculating current draws. For each column, calculate the cur-
rent and enter the total (in amperes) in the bottom row. When finished, copy the totals from Calcu-
lation Column 2 and Calculation Column 3 to Table 6.4 on page 41.

Device Type

Calculate Column 1

Primary, Non-Fire Alarm Current

(amps)

Calculate Column 2

Primary, Fire Alarm Current

(amps)

Calculation Column 3

Secondary, Non-Fire Alarm

Current

(amps)

Qty

X (current draw) = Total

Qty

X (current draw) =

Total

Qty

X (current draw) = Total

Main Circuit
Board

1

X [ 0.091] =

1

X [ 0.145] =

1

X [ 0.065] =

Power
Supervision Relay

[ ]

X [ 0.025] =

[ ]

X [0.025 ] =

[ ]

X [ 0.025] =

NAC/Output #1

[ ]

X [ ] =

NAC/Output #2

[ ]

X [ ] =

NAC/Output #3

[ ]

X [ ] =

NAC/Output #4

[ ]

X [ ] =

Current Draw
from TB4
Terminals 9 & 10

[ ] =

[ ] =

[ ] =

Sum each

column for totals

Primary Non-Alarm =

Primary Alarm =

Secondary Alarm =

Table 6.3 System Current Draw Calculations